RSR-550
5
.5
′′
Deep
AMCA 550 Listed Hurricane/
Storm
–
Resistant
Louver; extruded aluminum construction; frame
with channel profile; corner joints mitered and mechanically fastened, with
continuous recessed caulking
channel each side; intermediate mullions matching frame; gutters to drain rain water to jamb and mulli
–
on
downspouts; rated for an air performance and water penetration maintained effectiveness rate of 0.99
when tested in accor
dance with AMCA 500
–
L
PERFORMANCE
- Maintains Class A rating with 29mph wind velocity @ 3 in/hr rainfall rate @ Max. intake core velocity – 984 fpm ( 5 .0 m/s)
- Maintains Class B rating with 50mph wind velocity @ 8 in/hr rainfall rate @ Max. intake core velocity — 984 fpm (5 .0 m/s)
- Beginning point of water penetration (@0.01oz. / ft2 of free area) — 1, 250 fpm (6. 35 m/s)
- Free Area: 52.5 % , based on a test sample of 48 in (1219 mm) x 48 in (1219 mm)
- Pressure drop @ 1,000 fpm free area velocity — 0. 39 in. wg ( 97 Pa)
- Discharge loss coefficient Classification — Class 3
WIND DRIVEN PERFORMANCE
The louver test was based on a 39.375 in. (1.0 m) x 39.375 in. (1.0 m) core area unit tested at a
rainfall rate of 3 in. per hour (75 mm/hr) and with a wind directed to the face of the louver at a
velocity 29mph (13 m/s) as well as a rainfall rate of 8” per hour (203 mm) and a wind of 50 mph
(23.3 m/s). The test data shall show the water penetration ef
fectiveness rating at each
corresponding ventilation rate.