RSR-900
9
′′
Deep Storm Resistant Louver; extruded aluminum construction; frame with channel profile; corner joints
mitered and mechanically fastened, with continuous recessed caulking channel each side; intermediate
mullions matching frame; gutters to drain rain wate
r to jamb and mullion downspouts; rated for an air
performance and water penetration maintained effectiveness rate of 0.99 when tested in accordance with
AMCA 500
–
L.
PERFORMANCE
- Maintains Class A rating with 29mph wind velocity @ 3 in/hr rainfall rate @ M ax. intake core velocity – 888 fpm ( 4 . 5 m/s)
- Maintains Class A rating with 50mph wind velocity @ 8 in/hr rainfall rate @ Max. intake core velocity — 888 fpm ( 4. 5 m/s)
- Beginning point of water penetration (@0.01oz. / ft2 of free area) — 1,108 fpm ( 5.6 m/s)
- Free Area: 60 %, based on a test sample of 48 in (1219 mm) x 48 in (1219 mm)
- Intake pressure drop at beginning point of water penetration – 0. 35 in. wg ( 87 Pa
- Intake pressure drop @ 1,000 fpm free area velocity — 0. 30 in. wg ( 75 Pa)
- Intake Discharge loss coe fficient Classification — Class 3
- Exhaust Discharge loss coefficient Classification — Class 2
WIND DRIVEN PERFORMANCE
The louver test was based on a 39.375 in. (1.0 m) x 39.375 in. (1.0 m) core area unit tested at a
rainfall rate of 3 in. per hour (75
mm/hr) and with a wind directed to the face of the louver at a
velocity 29mph (13 m/s) as well as a rainfall rate of 8” per hour (203 mm) and a wind of 50 mph
(23.3 m/s). The test data shall show the water penetration effectiveness rating at each
correspon
ding ventilation rate.